FIT 9648

FIT 9648 – Flow Indicator Totaliser

Short description: A compact microcontroller-based single-channel flow indicator and totaliser with 4–20 mA input, 8-digit totaliser, batch counter, relay output, optional retransmission, and RS485 Modbus RTU. Designed for applications like flow monitoring, batching, dosing, and process control.

No serial information available.


FIT (48x96) Flow Indicator Totaliser
FIT (48×96) – Flow Indicator Totaliser

Key Features

  • Rugged, state-of-the-art microcontroller-based compact design.
  • Dual functionality: flow rate indication / 8-digit flow totalising and batch counter mode.
  • Accepts 4–20 mA DC input (linear or square root, factory set).
  • User-configurable flow rate and totaliser ranges, scalable via keypad.
  • Displays instantaneous flow rate (5-digit) or 8-digit totaliser (toggle by key).
  • One relay output, selectable for flow rate or totaliser setpoint (230 VAC, 1A).
  • Manual or optional remote reset for totaliser.
  • Built-in 24VDC, 100 mA excitation supply for powering transmitters.
  • True 4–20 mA retransmission output for external indicators, recorders, or PLCs.
  • Optional RS485 communication with MODBUS RTU protocol.
  • Battery-backed RAM for storing totaliser values and setpoints.
  • Compact 48 × 96 mm panel mounting enclosure.

Technical Specifications

  • Input: 4–20 mA DC, linear or square root (factory set)
  • Display: 7-segment LED; 5-digit for flow rate, 8-digit for totaliser
  • Resolution: 4½ digit for flow rate
  • Accuracy: ±0.3% of FS ±1 LSD (flow), ±2 counts (totaliser)
  • Totaliser: 8-digit; manual or optional remote reset
  • Keyboard: 4-key tactile keypad
  • Scaling: Flow rate and totaliser span/zero scalable via keypad
  • Relay Output: 1 relay, selectable for flow or totaliser; 230 VAC, 1A
  • Excitation Supply: 24VDC, 100 mA for external flow transmitter
  • Retransmission Output: True 4–20 mA retransmission; max load 500 Ω
  • Communication (Optional): RS485 with MODBUS RTU protocol
  • Remote Reset (Optional): via potential-free switch input
  • Data Storage: Totaliser value and setpoints in battery-backed RAM
  • Indications: LEDs for relay status and serial communication
  • Power Supply: 230 VAC or 110 VAC ±10%, 50 Hz, 1-phase (factory set)
  • Connections: Screw-type connectors
  • Mounting: Panel mount; Bezel: 48 × 96 mm (H × W); Depth: 120 mm; Cut-out: 46 × 92 mm